Addition of PSE [JOHB-SMP3 Protocol Set Error]
This error is issued when the DIP switch setting is inappropriate.
*In PRG: 01034 or earlier, this is oFA00 [Option Not Compatible with Port].
Table 2.3 Specifications of PSE Fault Code
Display (Hex.)
Name
ALM LED
Type
PSE (0437)
JOHB-SMP3 Protocol Set
Error
Illuminated
Fault
Table 2.4 Causes and Possible Solutions of PSE Faults
Code
Name
Cause
Possible Solutions
PSE
JOHB-SMP3 Protocol Set
Error
The DIP switch on the
JOHB-SMP3 is at its default
setting.
The protocol of
JOHB-SMP3 has not been
assigned.
Turn the drive OFF, then
reset the DIP switch on the
JOHB-SMP3 to a protocol
assigned state.
For details on DIP switch
specifications, refer to the
manual for JOHB-SMP3.
Table 2.5 Communication Monitor Data of PSE Faults
Register number (Hex.)
Description
00F5
Fault Description 12
bit 0-5
Reserved
bit 6
PSE [JOHB-SMP3 Protocol Set Error]
bit 7-F
Reserved

Table of Contents