5.3 UL Standards
256 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Drive Model
Maximum Applicable Motor Output
kW (HP)
Input Current Rating
A
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2110 30 (40) 111
FWH-225A
FWH-250A
*1
2138 37 (50) 136
FWH-275A
FWH-300A
*1
2169 45 (60) 164
FWH-275A
FWH-350A
*1
2211 55 (75) 200
FWH-325A
FWH-450A
*1
2257 75 (100) 271 FWH-600A
2313 90 (125) 324 FWH-800A
2360 110 (150) 394 FWH-1000B
2415 - - -
*1 Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Table 5.18 Factory-Recommended Branch Circuit Protection: 200 V Class (HD)
Drive Model
Maximum Applicable Motor Output
kW (HP)
Input Current Rating
A
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2004 0.55 (0.5) 3.6 FWH-45B
2006 0.75 (1) 4.8 FWH-45B
2010 1.5 (2) 8.9 FWH-45B
2012 2.2 (3) 12.7
FWH-50B
FWH-80B
*1
2018 3 (4) 17
FWH-80B
FWH-100B
*1
2021 3.7 (5) 20.7
FWH-80B
FWH-100B
*1
2030 5.5 (7.5) 30 FWH-125B
2042 7.5 (10) 40.3 FWH-150B
2056 11 (15) 58.2 FWH-200B
2070 15 (20) 78.4 FWH-225A
2082 18.5 (25) 96
FWH-225A
FWH-250A
*1
2110 22 (30) 82
FWH-225A
FWH-250A
*1
2138 30 (40) 111
FWH-275A
FWH-300A
*1
2169 37 (50) 136
FWH-275A
FWH-350A
*1
2211 45 (60) 164
FWH-325A
FWH-450A
*1
2257 55 (75) 200 FWH-600A
2313 75 (100) 271 FWH-800A
2360 90 (125) 324 FWH-1000B
2415 110 (150) 394 FWH-1000B
*1 Yaskawa recommends a fuse with a large rated current for applications with repeated loads.