Specifications
10
10.4 Model-Specific Specifications (400 V Class)
YASKAWA SIEPC71061705H GA700 Series Technical Manual 435
Table 10.8 Rating (400 V Class)
Model Input Voltage Duty Rating 4453 4568 4675
Maximum Applicable Motor Output (kW)
< 460 V
*1
HD1 220 250 315
ND1 250 315 355
≥ 460 V
*2
HD2 260 300 335
ND2 300 335 370
Maximum Applicable Motor Output (HP)
< 460 V
*1
HD1 300 335 400
ND1 335 400 450
≥ 460 V
*2
HD2 350 400 450
ND2 400 450 500
Input Rated Input Current (A)
< 460 V
HD1 (AC) 410 465 584
HD1 (DC) 502 569 715
ND1 (AC) 465 584 657
ND1 (DC) 569 715 805
≥ 460 V
HD2 (AC) 403 460 516
HD2 (DC) 494 563 632
ND2 (AC) 460 516 573
ND2 (DC) 563 632 702
Output
Rated Output Capacity
(kVA)
< 460 V
*3
HD1 272 298 398
ND1 298 374 444
≥ 460 V
*4
HD2 330 380 410
ND2 380 410 482
Rated Output Current
(A)
< 460 V
HD1 414 453 605
ND1 453 568 675
≥ 460 V
HD2 414 477 515
ND2 477 515 605
Overload Tolerance
• HD: 150% of the rated output current for 60 seconds The permitted
frequency of overload is one time each 10 minutes.
• ND: 110% of the rated output current for 60 seconds The permitted
frequency of overload is one time each 10 minutes.
Note:
Derating can be necessary for applications that start and stop
frequently.
Carrier Frequency
HD: 2 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 5 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
• AOLVand EZOLV: 120 Hz
• CL-V/f, CLV, AOLV/PM, and CLV/PM: 400 Hz
• V/f, OLV, OLV/PM: 590 Hz
Measures for
Harmonics
DC reactor Standard internal characteristics
Braking Device Braking Transistor External options
EMC Filter
EMC Filter
IEC61800-3, C3
Factory option
• Models 4xxxB: There is a category C3 EMC filter in the drive.