10.4 Model-Specific Specifications (400 V Class)
434 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Model
Input
Voltage
Duty Rating 4140 4168 4208 4250 4296 4371 4389
Input
Rated Input
Current (A)
< 460 V
HD1 (AC)
105 142 170 207 248 300 373
HD1 (DC)
129 174 209 254 304 367 457
ND1 (AC)
142 170 207 248 300 373 410
ND1 (DC)
174 209 254 304 367 457 502
≥ 460 V
HD2 (AC)
86.9 118 141 171 232 289 346
HD2 (DC)
106.0 144 172 210 284 354 424
ND2 (AC)
118 141 171 232 289 346 403
ND2 (DC)
144 172 210 284 354 424 494
Output
Rated Output
Capacity
(kVA)
< 460 V
*3
HD1
74 99 118 142 171 200 244
ND1
92 111 137 165
195
244 256
≥ 460 V
*4
HD2
76 99 124 143 191 241 288
ND2
99 124 143 191 241 288 330
Rated Output
Current (A)
< 460 V
HD1
112 150 180 216 260 304 371
ND1
140 168 208 250
296
371 389
≥ 460 V
HD2
96 124 156 180 240 302 361
ND2
124 156 180 240 302 361 414
Overload Tolerance
• HD: 150% of the rated output current for 60 seconds The permitted frequency of overload is one time each
10 minutes.
• ND: 110% of the rated output current for 60 seconds The permitted frequency of overload is one time each
10 minutes.
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 5 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 10 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
• AOLVand EZOLV: 120 Hz
• CL-V/f, CLV, AOLV/PM, and CLV/PM: 400 Hz
• V/f, OLV, OLV/PM: 590 Hz
Measures for
Harmonics
DC reactor Standard internal characteristics
Braking
Device
Braking Transistor
Standard internal
characteristics
External options
EMC Filter
EMC Filter
IEC61800-3, C3
Factory option
• Models 4xxxB: There is a category C3 EMC filter in the drive.
Power Supply
Rated Voltage, Rated Frequency
• Three-phase AC power supply 380 V to 480 Vat 50/60 Hz
• DC power supply 513 V to 679 V
Permitted Voltage Fluctuation -15% to +10%
Permitted Frequency Fluctuation ±5%
Input Power
(kVA)
< 460 V
HD1
84 113 135 165 198 239 297
ND1
113 135 165 198 239 297 327
≥ 460 V
HD2
72 98 117 142 193 240 288
ND2
98 117 142 193
295
288 335
*1 The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2 The maximum applicable motor output complies with 460 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*3 The rated output capacity is calculated with a rated output voltage of 380 V.