Mechanical Installation
2
2.7 Install the Keypad in a Control Panel or Another Device
YASKAWA SIEPC71061705H GA700 Series Technical Manual 45
*1 Minimum bending radius
Mount to the Outside of Control Panel
1. Use the dimensions in Figure 2.11 and Table 2.9 to cut an opening in the control panel for the keypad.
Figure 2.11 External/Face Mount Enclosure Panel Cut-Out Dimensions
Table 2.9 Panel Cut-Out Dimensions mm (in)
W H W1 H1 H2 H3 d
22
(0.89)
78
(3.07)
22
(0.89)
29
(1.14)
22
(0.89)
1
(0.04)
3.6
(0.14)
2. Remove the keypad and put the keypad connector in the holder on the front cover.
Note:
Insert the end of the keypad connector that has the tab.
A - Keypad
B - Keypad connector
C - Holder
Figure 2.12 Remove the Keypad
3. Put the keypad on the outside of the control panel.
Use M3 screws (6 mm (0.2 in) depth cross-recessed pan head screws) to attach the keypad from the
inside. Tighten the screws to a correct tightening torque:
M3 screws: 0.49 Nm to 0.73 Nm (4.34 lbfin to 6.46 lbfin)
A - Keypad
B - M3 screws
C - Enclosure panel
D - Screw mounting holes
Figure 2.13 Mount to the Outside of Control Panel