11.10 H: Terminal Functions
YASKAWA SIEPC71061705H GA700 Series Technical Manual 527
Setting Value Function Description Ref.
97 DWEZ Digital Input 8
Sets the DriveWorksEZ digital input 8. Refer to the DriveWorksEZ online manual for more information.
821
9F DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
ON : Disabled
OFF : Enabled
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Enabled/Disabled wDigital Input] to use this function.
821
101 !LOCAL/REMOTE
Selection
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
ON : REMOTE
OFF : LOCAL
821
102 !External Reference 1/2
Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
ON : b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
OFF : b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
821
103 !Multi-Step Speed
Reference 1
Uses a combination of multi-step speed references 1, 2 and 3 (N.C.) to set d1-01 to d1-08 [Multi-Step Speed
Reference].
821
104 !Multi-Step Speed
Reference 2
Uses a combination of multi-step speed references 1, 2 and 3 (N.C.) to set d1-01 to d1-08 [Multi-Step Speed
Reference].
821
105 !Multi-Step Speed
Reference 3
Uses a combination of multi-step speed references 1, 2 and 3 (N.C.) to set d1-01 to d1-08 [Multi-Step Speed
Reference].
821
106 !Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17 [Jog Reference]. The JOG
Frequency Reference (JOG command) overrides the d1-01 to d1-16 [References 1 to 16].
821
107 !Accel/Decel Time
Selection 1
Sets the drive to use C1-01, C1-02 [Acceleration/Deceleration Time 1] or C1-03, C1-04 [Acceleration/
Deceleration Time 2].
821
10A !Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal deactivates, retains the output
frequency that was stored in the drive at the time of the pause, and restarts motor operation.
821
10B !Overheat Alarm (oH2)
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal deactivates. The alarm
does not have an effect on drive operation.
821
10C !Analog Terminal Enable
Selection
Enables and disables the terminal selected with the H3-14 [Analog Input Term Enable Select] function.
ON : Input to the terminal selected with H3-14 is disabled
OFF : Input to the terminal selected with H3-14 is enabled
821
10D !Ignore Speed Fdbk (V/f
w/o Enc)
When the terminal deactivates, the drive ignores the feedback control from the encoder and operates in V/f control.
When the terminal activates, the drive uses the feedback from the encoder to control the motor speed again.
ON : Speed feedback control enable (Closed Loop V/f Control)
OFF : Speed feedback control disable (V/f Control)
821
10E !ASR Integral Reset
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : PI control
OFF : P control
821
110 !Up Command
Set this function and 111 [! Down Command] together. Sets the Up command and Down command to use the two
push button switches to increase and decrease the drive frequency reference.
ON : Holds the current frequency reference.
OFF : Increases the frequency reference.
821
111 !Down Command
Set this function and 110 [!Up Command] together. Sets the Up command and Down command to use the two push
button switches to increase and decrease the drive frequency reference.
ON : Holds the current frequency reference.
OFF : Decreases the frequency reference.
821
114 !Fault Reset
Sets the command to reset the current fault when the Run command is not active.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command
before you try to reset a fault.
821