11.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA SIEPC71061705H GA700 Series Technical Manual 597
*10 The maximum value changes when A1-02 changes:
When A1-02 = 5 [PM Open Loop Vector], the maximum value is 590.0 Hz.
When A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector], the maximum value is 100.0%.
When A1-02 = 8 [EZ Vector Control], the maximum value is 120.0 Hz.
*11 The minimum value changes when A1-02 changes:
When A1-02 = 5 [PM Open Loop Vector], the minimum value is -590.0 Hz.
When A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector], the minimum value is -100.0%.
When A1-02 = 8 [EZ Vector Control], the minimum value is -120.0 Hz.