11.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
596 YASKAWA SIEPC71061705H GA700 Series Technical Manual
No. Name Range Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
EZOLV
(8)
F1-01
Encoder 1 Pulse Count
(PPR)
0 - 60000 1 ppr - - 1024 -
F1-05
Encoder 1 Rotation
Selection
0 - 1 1 - - 1 -
F1-09
Overspeed Detection
Delay Time
0.0 - 2.0 0.1 s - 0.0 0.0 0.0
L1-01
Motor Overload (oL1)
Protection
0 - 6 1 4 4 5 1
*8
L2-31
KEB Start Voltage
Offset Level
0 - 100
*7
1 V 50 50 50 50
L3-05
Stall Prevention during
RUN
0 - 3 1 1 - - 3
L3-20
DC Bus Voltage
Adjustment Gain
0.00 - 5.00 0.01 0.65 0.65 0.65 0.65
L3-21
OVSuppression Accel/
Decel P Gain
0.10 - 10.00 0.01 1.00 1.00 1.00 1.00
L3-36
Current Suppression
Gain@Accel
0.0 - 100.0 0.1 - - - -
L4-01
Speed Agree Detection
Level
0.0 - 590.0
*10
0.1 0.0 Hz 0.0% 0.0% 0.0 Hz
L4-02
Speed Agree Detection
Width
0.0 - 20.0
*4
0.1 2.0 Hz 4.0% 4.0% 2.0 Hz
L4-03
Speed Agree Detection
Level(+/-)
-590.0 - +590.0
*10
*11
0.1 0.0 Hz 0.0% 0.0% 0.0 Hz
L4-04
Speed Agree Detection
Width(+/-)
0.0 - 20.0
*4
0.1 2.0 Hz 4.0% 4.0% 2.0 Hz
L8-38
Carrier Frequency
Reduction
0 - 2 1 0 - 0 0
L8-40
Carrier Freq Reduction
Off-Delay
0.00 - 2.00 0.01 s 0.00 - 0.00 0.00
L8-90
STPo Detection Level
(Low Speed)
0 - 5000 1 0 80 - 0
n1-15
PWM Voltage Offset
Calibration
0 - 2 1 1 1 1 1
n5-04
Speed Response
Frequency
0.00 - 500.00 0.01 Hz - 20.00 50.00 -
n8-35
Initial Pole Detection
Method
0 - 2 1 0 1 1 -
n8-51
Pull-in Current @
Acceleration
0 - 200 1% 50% - - 80%
o1-03
Frequency Display
Unit Selection
0 - 3 1 0 1 1 0
*9
o1-04
V/f Pattern Display
Unit
0 - 1 1 - 1 1 0
*9
*1 The default setting is different for different models.
2138 - 2415, 4089 - 4675: 0.30
*2 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
*3 The setting range is 0.0 to 100.0 when A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector].
*4 The setting range is 0.0 to 40.0 when A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector].
*5 The default setting changes when C6-01 [Normal / Heavy Duty Selection] changes.
*6 The maximum value changes when A1-02 changes:
When A1-02 = 5 [PM Open Loop Vector], the maximum value is 590.0 Hz. The maximum value of the setting range changes
when E5-01 [PM Motor Code Selection] changes. When E5-01 = FFFF [PM Motor Code Selection = FFFF], the maximum
value is 590.0 Hz.
When A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector], the maximum value is 400.0 Hz. The
maximum value of the setting range changes when E5-01 changes. When E5-01 = FFFF, the maximum value is 400.0 Hz.
*7 This is the value for 200 V class drives. Double the value for 400 V class drives.
*8 The default setting changes when E9-01 [Motor Type Selection] changes.
E9-01 = 0 [Induction (IM)]: 1
E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 4
*9 The default setting changes when E9-01 [Motor Type Selection] changes.
E9-01 = 0 [Induction (IM)]: 0
E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 1