Parameter List
11
11.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA SIEPC71061705H GA700 Series Technical Manual 605
No.
*1
Name Unit Default
- Drive Model - 2042 2056 2070 2082
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 6B 6D 6E 6F
E2-11
(E4-11)
Motor Rated
Power
kW 7.5 11 11 15 15 18.5 18.5 22
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy Saving
Coefficient
Value
- 72.69 70.44 70.44 63.13 63.13 57.87 57.87 51.79
C5-17
(C5-37)
Motor Inertia kgm
2
0.037 0.053 0.053 0.076 0.076 0.138 0.138 0.165
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 26.6 39.7 39.7 53 53 65.8 65.8 77.2
E2-02
(E4-02)
Motor Rated
Slip
Hz 1.3 1.7 1.7 1.6 1.6 1.67 1.67 1.7
E2-03
(E4-03)
Motor No-
Load Current
A 8 11.2 11.2 15.2 15.2 15.7 15.7 18.5
E2-05
(E4-05)
Motor Line-
to-Line
Resistance
Ω 0.288 0.23 0.23 0.138 0.138 0.101 0.101 0.079
E2-06
(E4-06)
Motor
Leakage
Inductance
% 15.5 19.5 19.5 17.2 17.2 15.7 20.1 19.5
E2-10
(E4-10)
Motor Iron
Loss
W 262 245 245 272 272 505 505 538
E5-01
PM Motor
Code
Selection
- 120B 120B 120D 120D 120E 120E 120F 120F
L2-02
Power Loss
Ride Through
Time
s 1 1 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 0.8 0.9 0.9 1 1 1 1 1
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.3 0.3 0.3 0.6 0.6 0.6 0.6 0.6
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190 190 190
L3-24
Motor Accel
Time @ Rated
Torque
s 0.175 0.265 0.265 0.244 0.244 0.317 0.317 0.355
L8-02
Overheat
Alarm Level
°C 110 110 115 115 120 120 133 130
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10