Parameter Details
12
12.2 A: Initialization Parameters
YASKAWA SIEPC71061705H GA700 Series Technical Manual 625
1. Push or to select “A: Initialization Parameters”, then push .
2. Push or to select [A1-04], then push .
You can now change parameter settings.
3. Push or to move the digit and enter the password.
4. Push to confirm the password.
The drive unlocks the parameters and automatically shows the Parameters Screen.
5. Push or to show [A1-02], then push .
The keypad shows the setting value for [A1-02].
6. Push or to make sure that you can change the setting value.
Push (Back) until the keypad shows the Parameter Setup Mode screen.
■ A1-05: Password Setting
No.
(Hex.)
Name Description
Default
(Range)
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter the correct
password in A1-04 [Password] to unlock parameters and accept changes.
0000
(0000 - 9999)
This parameter can lock these parameter settings:
• A1-01 [Access Level Selection]
• A1-02 [Control Method Selection]
• A1-03 [Initialize Parameters]
• A1-06 [Application Preset]
• A1-07 [DriveWorksEZ Function Selection]
• A2-01 to A2-32 [User Parameter 1 to 32]
Note:
• Usually, the keypad will not show A1-05. To show and set A1-05, show A1-04 [Password] and then push and on the
keypad at the same time.
• After you set A1-05, the keypad will not show it again until you enter the correct password in A1-04. Make sure that you remember the
A1-05 setting value. If you do not know the A1-05 setting value, contact Yaskawa or your nearest sales representative.
• When A1-03 = 2220, 3330 [2-Wire Initialization, 3-Wire Initialization], the drive is initialized to A1-05 = 0000. Be sure to set the
password again when a password is necessary for the application.
• Change the setting value in A1-05 to change the password. The new setting value becomes the new password.
• When you use the password to unlock and change a parameter, enter a value other than the password in A1-04 to lock the parameter
again with the same password.
• If A1-04 ≠ A1-05, MEMOBUS Communication cannot read or write A1-05.
■ A1-06: Application Preset
WARNING! Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06 ≠ 0), it changes the I/O terminal functions for
the drive and it can cause equipment to operate unusually. This can cause serious injury or death.
No.
(Hex.)
Name Description
Default
(Range)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0
(0 - 7)
The drive software contains the application presets shown below. Set A1-06 to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters
frequently used for the application in parameters A2-01 to A2-16 [User Parameters 1 to 16] for easy configuration
and reference in [User Custom Parameters] in the main menu.
• Water supply pump
• Conveyor
• Exhaust fan
• HVAC fan