12.2 A: Initialization Parameters
626 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Air compressor
Crane (hoist)
Crane (traveling)
Note:
Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization]
to initialize parameters.
After you set A1-06 for a hoist application (A1-06 = 6 or 7), make sure that you do Auto-Tuning.
It is not possible to change the A1-06 value. To set an application preset, first set A1-03 = 2220 to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
If you set A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms] to set parameters to A2-17 to A2-32 [User
Parameters 17 to 32] automatically, the drive will reset these parameters when you change the A1-06 setting.
0 : General-purpose
The drive saves the parameters in Table 12.3 as user parameters.
Table 12.3 Parameters Saved as User Parameters with the General-purpose Preset
User Parameter No. Parameter No. Saved Name
A2-01
A1-02 Control Method Selection
A2-02
b1-01 Frequency Reference Selection 1
A2-03
b1-02 Run Command Selection 1
A2-04
b1-03 Stopping Method Selection
A2-05
C1-01 Acceleration Time 1
A2-06
C1-02 Deceleration Time 1
A2-07
C6-01 Normal / Heavy Duty Selection
A2-08
C6-02 Carrier Frequency Selection
A2-09
d1-01 Reference 1
A2-10
d1-02 Reference 2
A2-11
d1-03 Reference 3
A2-12
d1-04 Reference 4
A2-13
d1-17 Jog Reference
A2-14
E1-01 Input AC Supply Voltage
A2-15
E1-03 V/f Pattern Selection
A2-16
E1-04 Maximum Output Frequency
A2-17 E1-05 Maximum Output Voltage
A2-18 E1-06 Base Frequency
A2-19 E1-09 Minimum Output Frequency
A2-20 E1-13 Base Voltage
A2-21 E2-01 Motor Rated Current (FLA)
A2-22 E2-04 Motor Pole Count
A2-23 E2-11 Motor Rated Power
A2-24 H4-02 Terminal FM Analog Output Gain
A2-25 L1-01 Motor Overload (oL1) Protection
A2-26 L3-04 Stall Prevention during Decel
1 : Water Supply Pump 2
The drive automatically sets the parameters in Table 12.4 for a water supply pump application.
Table 12.4 Best Parameter Settings for Water Supply Pump Applications
No. Name Optimal Value
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Disabled
C1-01 Acceleration Time 1 1.0 s
C1-02 Deceleration Time 1 1.0 s