Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061705H GA700 Series Technical Manual 789
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
F6-45: BACnet Node Address
No.
(Hex.)
Name Description
Default
(Range)
F6-45
(02FB)
BACnet Node Address
Sets the node address for BACnet communication.
1
(0 - 127)
F6-46: BACnet Baud Rate
No.
(Hex.)
Name Description
Default
(Range)
F6-46
(02FC)
BACnet Baud Rate
Sets the BACnet communications speed.
3
(0 - 8)
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
F6-47: Rx to Tx Wait Time
No.
(Hex.)
Name Description
Default
(Range)
F6-47
(02FD)
Rx to Tx Wait Time
Sets the wait time for the drive to receive and send BACnet communication.
5 ms
(5 - 65 ms)
F6-48: BACnet Device Object Identifier0
No.
(Hex.)
Name Description
Default
(Range)
F6-48
(02FE)
BACnet Device Object
Identifier0
Sets the last word of BACnet communication addresses.
0
(0 - FFFF)
F6-49: BACnet Device Object Identifier1
No.
(Hex.)
Name Description
Default
(Range)
F6-49
(02FF)
BACnet Device Object
Identifier1
Sets the last word of BACnet communication addresses.
0
(0 - 3F)
F6-50: DeviceNet MAC Address
No.
(Hex.)
Name Description
Default
(Range)
F6-50
(03C1)
DeviceNet MAC Address
Sets the MAC address for DeviceNet communication. Restart the drive after you change the
parameter setting.
0
(0 - 64)
Note:
Be sure to set a MAC address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings
will cause AEr [Station Address Setting Error] errors and the MS LED on the option will flash.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Related product manuals