EasyManua.ls Logo

YASKAWA GA700 Series

YASKAWA GA700 Series
1021 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.8 H: Terminal Functions
808 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Figure 12.83 shows an example of how Up/Down command operates. In this example, the lower limit value of the
frequency reference is set in d2-02. Figure 12.83 shows the time chart when Freq Reference Retention Select [d4-
01] is enabled and disabled.
Figure 12.83 Up/Down Command Time Chart
11: Down Command
Setting Value Function Description
11 Down Command
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting 10 [Up
Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
Note:
If you set only the Up command or only the Down command, the drive will detect oPE03 [Multi-Function Input Setting Err].
If you set two or more of these functions at the same time, the drive will detect oPE03:
Up/Down command
Accel/Decel Ramp Hold
Reference Sample Hold
Offset Frequency 1, 2, 3 addition
Up/Down 2 Command
The Up/Down command does not function in these conditions:
b1-01 = 2, 3 [Frequency Reference Selection 1 = Memobus/Modbus Communications, Option PCB]
b1-02 1 [Run Command Selection 1 Control Circuit Terminal]
Drive is in LOCAL mode
Set to b1-15 [Frequency Reference Selection 2] by use of H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection]
When you enter the UP command, the frequency reference increases. When you enter the Down command, the
frequency reference decreases.
The Up and Down commands have priority over all other frequency references. When you enable the Up/Down
command, the drive will ignore these frequency references:
Frequency reference from Keypad [b1-01 = 0]
Frequency reference from Analog Input [b1-01 = 1]
Frequency reference from Pulse Train Input [b1-01 = 4]
12: Forward Jog
Setting Value Function Description
12 Forward Jog
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Related product manuals