12.8 H: Terminal Functions
834 YASKAWA SIEPC71061705H GA700 Series Technical Manual
OFF : The drive is not in baseblock.
9: Frequency Reference from Keypad
Setting Value Function Description
9 Frequency Reference from
Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
A: Run Command from Keypad
Setting Value Function Description
A Run Command Source
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
B: Torque Detection 1 (N.O.)
Setting Value Function Description
B Torque Detection 1 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque <
L6-02 for longer than the time set in L6-03 [Torque Detection Time 1].
Note:
When L6-01 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
Refer to L6: Torque Detection on page 900 for more information.
C: Frequency Reference Loss
Setting Value Function Description
C Frequency Reference Loss
The terminal activates when the drive detects a loss of frequency reference.
Note:
Refer to L4-05: Fref Loss Detection Selection for more information.
D: Braking Resistor Fault
Setting Value Function Description
D Braking Resistor Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.
E: Fault
Setting Value Function Description
E Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
F: Not Used
Setting Value Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure signals from the PLC.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Related product manuals