12.8 H: Terminal Functions
YASKAWA SIEPC71061705H GA700 Series Technical Manual 865
Figure 12.117 Simple Closed Loop Speed Control Block Diagram
Enable Simple Closed Loop V/f Mode
1. Connect the encoder output pulse wiring to terminal RP.
2. Set A1-02 = 0 [Control Method Selection = V/f Control].
3. Set H6-01 = 3.
4. Set H6-02 [Terminal RP Frequency Scaling] to the speed feedback (pulse train input signal) frequency at the
time when the frequency reference is 100%.
Make sure that H6-04 [Terminal RP Function Bias] = 0% and H6-03 [Terminal RP Function Gain] = 100%.
5. Select the detection method for the direction of motor rotation.
When you use an MFDI, set H1-xx = 7E.
6. Set C5 parameters related to ASR gain and integral time to adjust responsiveness.
Note:
Set A1-02 = 0 and H6-01 = 3 to show C5 parameters.
You cannot use Simple Closed Loop V/f Mode with the Motor Switch function.
H6-02: Terminal RP Frequency Scaling
No.
(Hex.)
Name Description
Default
(Range)
H6-02
(042D)
RUN
Terminal RP Frequency
Scaling
Sets the frequency of the pulse train input signal used when the item selected with H6-01
[Terminal RP Pulse Train Function] is input at 100%.
1440 Hz
(100 - 32000 Hz)
H6-03: Terminal RP Function Gain
No.
(Hex.)
Name Description
Default
(Range)
H6-03
(042E)
RUN
Terminal RP Function Gain
Sets the gain used when the function in H6-01 [Terminal RP Pulse Train Function] is input to
terminal RP.
100.0%
(0.0 - 1000.0%)
H6-04: Terminal RP Function Bias
No.
(Hex.)
Name Description
Default
(Range)
H6-04
(042F)
RUN
Terminal RP Function Bias
Sets the bias used when the function in H6-01 [Terminal RP Pulse Train Function] is input to
terminal RP. Sets a value at the time when the pulse train is 0 Hz.
0.0%
(-100.0 - 100.0%)
H6-05: Terminal RP Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H6-05
(0430)
RUN
Terminal RP Filter Time
Sets the time constant for the pulse train input primary delay filters.
0.10 s
(0.00 - 2.00 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Related product manuals