Parameter Details
12
12.9 L: Protection Functions
YASKAWA SIEPC71061705H GA700 Series Technical Manual 889
Figure 12.135 Current Limit Acceleration
■ L3-02: Stall Prevent Level during Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-02
(0490)
Stall Prevent Level during
Accel
Sets the output current level to activate the Stall Prevention function during acceleration as a
percentage of the drive rated output current.
Determined by C6-01 and
L8-38
(0 - 150%)
Note:
• If you use a motor that is small compared to the drive and the motor stalls, decrease the setting value.
• When you operate the motor in the constant power range, set L3-03 [Stall Prevent Limit during Accel].
• The upper limit of the setting range changes when C6-01 [Normal / Heavy Duty Selection] changes.
–150% when C6-01 = 0 [Heavy Duty Rating].
–110% when C6-01 = 1 [Normal Duty Rating].
■ L3-03: Stall Prevent Limit during Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-03
(0491)
Stall Prevent Limit during
Accel
Sets the lower limit for the stall prevention level used in the constant output range as a percentage
of the drive rated output current.
50%
(0 - 100%)
The stall prevention level set in L3-02 [Stall Prevent Level during Accel] is automatically reduced when the motor
is running within the constant output range. Parameter L3-03 is the limit value used to prevent the stall prevention
level during constant output ranges to fall below the minimum required level.
Note:
The function to automatically reduce the stall prevention level does not operate when L3-01 = 3 [Stall Prevention during Accel =
Current Limit Method].
Figure 12.136 Stall Prevent Level during Accel/Limit
■ L3-04: Stall Prevention during Decel
No.
(Hex.)
Name Description
Default
(Range)
L3-04
(0492)
Stall Prevention during
Decel
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
1
(Determined by A1-02)