EasyManua.ls Logo

YASKAWA GA700 Series

YASKAWA GA700 Series
1021 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.9 L: Protection Functions
YASKAWA SIEPC71061705H GA700 Series Technical Manual 901
Table 12.75 Overtorque/Undertorque Detection Parameters
Configuration Parameter Overtorque/Undertorque Detection 1 Overtorque/Undertorque Detection 2
MFDO Function Select
Terminal M1-M2
Terminal M3-M4
Terminal M5-M6
H2-01, H2-02, and H2-03 = B
N.O.: Activated when detected
H2-01, H2-02, and H2-03 = 18
N.O.: Activated when detected
H2-01, H2-02, and H2-03 = 17
N.C.: Deactivated when detected
H2-01, H2-02, and H2-03 = 19
N.C.: Deactivated when detected
Detection conditions and selection of operation after
detection
L6-01 L6-04
Detection Level L6-02 L6-05
Analog Input Terminal
*1
H3-xx = 7
-
Detection Time L6-03 L6-06
*1 You can also use an analog input terminal to supply the torque detection level. To enable this function, set H3-xx = 7 [MFAI Function
Selection = Overtorque/Undertorque DetectLvl]. If you set L6-02 and H3-xx = 7, the analog input is most important and the drive
disables L6-02.
You cannot use Overtorque/Undertorque Detection 2 to set the detection level for the analog input terminals.
Note:
The drive sets the Overtorque/Undertorque detection level in these conditions:
V/f, CL-V/f, OLV/PM: Current level (drive rated current = 100%)
OLV, CLV, AOLV, AOLV/PM, CLV/PM, EZOLV: Motor torque (Motor rated torque = 100%)
L6-08 0 [Mechanical Fatigue Detect Select Disabled]: Current level (drive rated output current = 100%)
Time Chart for Detection of Overtorque/Undertorque
Overtorque Detection Time Chart
When you use Overtorque/Undertorque Detection 1, the drive detects overtorque if the motor current or motor
torque is at the detection level set in L6-02 [Torque Detection Level 1] for the time set in L6-03 [Torque Detection
Time 1]. Parameter L6-01 [Torque Detection Selection 1] sets the operation after detection.
When you use Overtorque/Undertorque Detection 2, set L6-04 [Torque Detection Selection 2], L6-05 [Torque
Detection Level 2], and L6-06 [Torque Detection Time 2].
Use H2-01 to H2-03 [MFDO Function Select] to set the terminal that outputs the alarm.
Figure 12.142 Overtorque Detection Time Chart
Note:
The drive applies a hysteresis of approximately 10% of the drive rated output current or the motor rated torque to the overtorque/
undertorque detection function.
Undertorque Detection Time Chart
When you use Overtorque/Undertorque Detection 1, the drive detects undertorque if the motor current or motor
torque is less than or equal to the detection level set in L6-02 for the time set in L6-03. Parameter L6-01 sets the
operation after detection.
When you use Overtorque/Undertorque Detection 2, set the operation in L6-04, L6-05, and L6-06.
Use H2-01 to H2-03 [MFDO Function Select] to set the terminal that outputs the alarm.

Table of Contents

Related product manuals