3.5 Control Circuit Wiring
98 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Main Circuit Power Supply External 24 V Power Supply
o2-23
[External 24V Powerloss
Detection]
o2-26
[Alarm Display at Ext. 24V
Power]
Alarm Display
OFF ON - 0 [Disabled] Ready LED light flashes
quickly
- 1 [Enabled] EP24v [External Power 24V
Supply]
Operation When Using External 24 V Power Supply
To operate the drive, de-energize the main circuit power supply and connect an external 24 V power supply to
terminals PS-AC.
Function Operation Solution
Keypad The keypad operates the same as when the main circuit power supply
is ON. The drive will not detect oPr [Keypad Connection Fault].
-
Data Log The data log function operates the same as when the main circuit
power supply is ON.
The operation is different for different drive software versions.
*1
-
Communications by Communication Option
or MEMOBUS/Modbus Communication
Terminals
Communication operates the same as when the main circuit power
supply is ON. -
MFAI MFAI operates the same as when the main circuit power supply is
ON.
-
MFAO MFAO operates the same as when the main circuit power supply is
ON.
-
MFDI MFDI does not operate when the main circuit power supply of the
drive is OFF.
Connect the external 24 V power supply to the MFDI
selection common terminal (SC).
*2
MFDO
Multi-Function Photocoupler Output
Fault Relay Output Terminal
MFDO operates the same as when the main circuit power supply is
ON.
The operations of MFDO terminals and fault relay output terminals
set for H2-xx = E [Fault] are different for different drive software
versions.
*3
-
Pulse Train Input Pulse train input operates the same as when the main circuit power
supply is ON.
-
Pulse train output Pulse train output operates the same as when the main circuit power
supply is ON.
-
Encoder Option Speed Detection (PG-B3,
PG-X3, PG-F3, PG-RT3)
Encoder options do not operate when the main circuit power supply of
the drive is OFF.
The operation to detect encoder option-related faults is different for
different software versions.
When you use an encoder, make sure that the drive main
circuit power supply is ON.
*4
Analog Input Option (AI-A3) Analog input options operate the same as when the main circuit power
supply is ON.
-
Analog Output Option (AO-A3) Analog output options operate the same as when the main circuit
power supply is ON.
The operation is different for different drive software versions.
*5
-
Digital Input Option (DI-A3) Digital input options do not operate when the main circuit power
supply of the drive is OFF.
Connect the external 24 V power supply to the Input
signal common terminal (SC).
*2
Digital Output Option (DO-A3) Digital output options operate the same as when the main circuit
power supply is ON.
-
*1 When you use an external 24 V power supply, the operation of the data log function is different for different drive software versions.
On drives with software versions PRG: 09015 and later, you can continue the data log function.
Note:
The PRG column on the nameplate on the right side of the drive identifies the software version. You can also use U1-25
[SoftwareNumber FLASH] to identify the software version.
*2 When you use MFDI and a Digital Input option (DI-A3), wire the terminals as shown in Wiring MFDI Terminals on page 99 or
Wiring Digital Input Option (DI-A3) on page 99.
*3 When you use an external 24 V power supply, the operation of the MFDO terminals are different for different drive software
versions.
Note:
The PRG column on the nameplate on the right side of the drive identifies the software version. You can also use U1-25
[SoftwareNumber FLASH] to identify the software version.
Drive software versions PRG: 01028 and later
When the main circuit power supply of the drive turns off, and you remove the cause of a fault and do a fault reset from the
keypad, the fault relay output terminals and the MFDO terminals set for H2-xx = E, 10E [Fault] will change status.
Drive software versions PRG: 01027 and earlier
When the main circuit power supply of the drive turns off, remove the cause of a fault and do a fault reset from the keypad. The
fault relay output terminals and the MFDO terminals set for H2-xx = E, 10E [Fault] will keep the same status as before the main
circuit power supply of the drive turned off. The fault code shown on the keypad will disappear.