InteliDrive DCU Marine - 3.0.0 Global Guide
112
Setpoint group Basic settings Related FW 3.0.0
Range [units] 1 .. 500 [-]
Default value 120
Step 1
Comm object 8252 Related applications All
Config level Standard
Setpoint visibility Always
Description
Number of teeth on the engines flywheel for the pick-up. Setpoint (RPM pickup measuring) is ignored
when RPM is received via J1939.
Gear Teeth
6 back to List of setpoints
Setpoint group Basic settings Related FW 3.0.0
Range [units] 1 .. 500 [-]
Default value 120
Step 1
Comm object 10920 Related applications All
Config level Standard
Setpoint visibility Always
Description
Number of teeth on the engines flywheel for the pick-up connected to ID-RPU.
RPUGear Teeth
6 back to List of setpoints
Setpoint group Basic settings Related FW 3.0.0
Range [units] 30 .. 4000 [RPM]
Default value 1500
Step 1
Comm object 8253 Related applications All
Config level Standard
Setpoint visibility Always
Description
Nominal engine speed, base for Overspeed protection limit and Engine Values: Speed Request percentage
calculation.
Note: Nominal RPM must correspond to 100% Throttle position in ECU for correct Load sharing function
in PRP application.
Nominal RPM
6 back to List of setpoints