InteliDrive DCU Marine - 3.0.0 Global Guide
172
Setpoint group DetCon20 Related FW 3.0.0
Range [units] 0,0 .. 100,0 [%/s]
Default value 30,0 %/s YES
Step 0,1 %/s
Comm object 10300 Related applications All
Config level Standard
Setpoint visibility DetCon20 support configured
Description
Decrease ramp specifies rate at which is the timing reduction signal (analog output) decreased as soon as
knocking drops below the IgnRedLimit (ignition reduction limit).
DecreaseRamp
6 back to List of setpoints
Setpoint group DetCon20 Related FW 3.0.0
Range [units] 0 .. 255 [-]
Default value 10 YES
Step 1
Comm object 10299 Related applications All
Config level Standard
Setpoint visibility DetCon20 support configured
Description
Ignition reduction limit is knocking value above which the engine is considered to be knocking. If the value is
exceeded, DetCon20 binary output ENGINE KNOCKING is activated and the values assigned to the timing
reduction are altered.
IgnRedLimit
6 back to List of setpoints
Setpoint group DetCon20 Related FW 3.0.0
Range [units] 0 .. 255 [-]
Default value 40 YES
Step 1
Comm object 10304 Related applications All
Config level Standard
Setpoint visibility DetCon20 support configured
Description
Immediate stop limit is knocking value above which DetCon20 binary output TRIP is activated. This causes
engine to shut down if properly wired.
ImmStopLimit
6 back to List of setpoints