InteliDrive DCU Marine - 3.0.0 Global Guide
121
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [9600, 19200, 38400, 57600, 115200] [bps]
Default value 9600
Step [-]
Comm object 24420 Related applications All
Config level Standard
Setpoint visibility Always
Description
The setpoint adjusts communication speed of the RS485 interface when RS485 Mode (page 121) is set to
MODBUS.
RS485 MBCSpd
6 back to List of setpoints
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [STANDARD, MODBUS, ECULINK]
Default value STANDARD
Step [-]
Comm object 24451 Related applications All
Config level Standard
Setpoint visibility Always
Description
Communication protocol selection.
STANDARD: InteliDrive (DriveConfig, InteliMonitor, Remote panel) communication protocol.
MODBUS: Modbus RTU protocol.
ECULINK: Connection to an electronic-controlled engine which uses non-J1939 ECU. The proper
ECU type must be also configured with GenConfig.
Note: Detailed description of Modbus protocol include some examples, see in InteliGen Communication
guide.
RS485 Mode
6 back to List of setpoints