InteliDrive DCU Marine - 3.0.0 Global Guide
137
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 1
Step 1
Comm object 10131 Related applications All
Config level Standard
Setpoint visibility Always
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 1. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 1. For details see BinInp
Delay 3 (page 138) description.
BinInp Delay 1
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 5
Step 1
Comm object 10132 Related applications All
Config level Standard
Setpoint visibility Always
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 2. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 2. For details see BinInp
Delay 3 (page 138) description.
BinInp Delay 2
6 back to List of setpoints