InteliDrive DCU Marine - 3.0.0 Global Guide
145
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10141 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Warning characteristic is defined by two points for Idle RPM and Nominal RPM.OPNomRPMWrn
defines oil pressure warning level at nominal speed. For details see OilPrRPMdel description.
OPNomRPMWrn
6 back to List of setpoints
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10142 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.OPIdleRPMSd
defines oil pressure shutdown level at idle speed. For details see OilPrRPMdel (page 146) description.
OPIdleRPMSd
6 back to List of setpoints
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0 YES
Step 0,1
Comm object 10143 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.OPNomRPMSd
defines oil pressure shutdown level at nominal speed. For details see OilPrRPMdel (page 146) description.
OPNomRPMSd