InteliDrive DCU Marine - 3.0.0 Global Guide
171
Setpoint group SCM unit Related FW 3.0.0
Range [units] 0 .. 500 [-]
Default value 0
Step 1
Comm object 10907 Related applications All
Config level Standard
Setpoint visibility Always
Description
Conversion ratio (number of pulses for increase by 1) for ID-SCM IMP 2 impulse input / SCM Imp2 value.
Frequency range max. 60 Hz.
Input Setpoint Value
RPM1 FreqRate1 SCM Freq1
RPM2 FreqRate2 SCM Freq2
IMP1 TransferRate1 SCM Imp1
IMP2 TransferRate2 SCM Imp2
Example: To measure actual water flow in liters (or cubic meters) per minute set FreqRate = 10 []
when sensor gives 10 pulses per liter (or cubic meters).
Example: To measure total water consumption in liters (or cubic meters) set TransferRate = 100 []
when sensor gives 100 pulses per 1liter (or cubic meter).
TransferRate2
6 back to List of setpoints
DetCon20
Setpoint group DetCon20 Related FW 3.0.0
Range [units] 0,0 .. 25,4 [s]
Default value 1,0 s YES
Step 0,1 s
Comm object 10303 Related applications All
Config level Standard
Setpoint visibility DetCon20 support configured
Description
Delay after load reduction defines delay of timing signal reduction process after knocking level drops below
the IgnRedLimit.
DelayLoadRed
6 back to List of setpoints