EasyManua.ls Logo

ComAp InteliDrive DCU Marine - Operational; Timer Active; Alarm Blinkact; Common Sdo;Derating Alarm

ComAp InteliDrive DCU Marine
285 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive DCU Marine - 3.0.0 Global Guide
210
Related FW 3.0.0 Related applications All
Comm object 61
Description
Output closes with binary output Prestart and opens with binary output Cooling pump (see AfterCoolTime
(page 129)
Operational
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 277
Description
Binary output Timer Active is closed and opened according to Timer setpoints setting. Engine starts and
stops when this output is connected (configured) to Binary input Rem Start/Stop. Timer is active in all
controller modes include OFF mode.
Timer Active
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 278
Description
It follows the panel Red LED. Starts blink after any (Wrn, Sd) Alarm is activated, light after Fault reset,
disappear after Fault reset when no alarm is active.
Alarm BlinkAct
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 251
Description
Indicates any active protection configured as Shut down Override.
Common SdO
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 279
Description
Power derating indication, information received from communication bus.
Derating Alarm
6 back to List of LBO

Table of Contents