InteliDrive DCU Marine - 3.0.0 Global Guide
120
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [STANDARD, MODBUS]
Default value STANDARD
Step [-]
Comm object 24522 Related applications All
Config level Standard
Setpoint visibility Always
Description
Communication protocol selection.
STANDARD: InteliDrive (DriveConfig, InteliMonitor, Remote panel) communication protocol.
MODBUS: Modbus RTU protocol.
Note: Detailed description of Modbus protocol include some examples, see in InteliGen Communication
guide.
RS232 Mode
6 back to List of setpoints
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [19200, 38400, 57600, 115200] [bps]
Default value 38400
Step [-]
Comm object 24341 Related applications All
Config level Standard
Setpoint visibility Always
Description
The setpoint adjusts communication speed of the RS232 interface when RS232 Mode (page 120) is set to
STANDARD.
Note: If the controller is connected to IB-NT via the RS232 interface, set the speed to 57600 - the
supported communication speed.
RS232 TermCSpd
6 back to List of setpoints