InteliDrive DCU Marine - 3.0.0 Global Guide
113
Setpoint group Basic settings Related FW 3.0.0
Range [units] [ISOCHRON, DROOP, BIN.INPUT]
Default value ISOCHRON
Step [-]
Comm object 10230 Related applications All
Config level Standard
Setpoint visibility Always
Description
Activates/deactivates the logical binary output Droop Sw, that can be configured as J1939 output to switch
ECU mode.
BIN.INPUT: ISOCH/DROOP mode is switched via Binary input BI Droop (DROOP when closed).
Governor Mode
6 back to List of setpoints
Setpoint group Basic settings Related FW 3.0.0
Range [units] [IDLE, NOMINAL, BIN.INPUT]
Default value IDLE
Step [-]
Comm object 10336 Related applications All
Config level Standard
Setpoint visibility Always
Description
Activates/deactivates the logical binary output Nominal Sw, that can be configured as J1939 output to
switch ECU.
BIN.INPUT: IDLE/NOMINAL mode is switched via Binary input BI Nominal (NOMINAL when closed).
Idle/Nominal
6 back to List of setpoints