InteliDrive DCU Marine - 3.0.0 Global Guide
139
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 0
Step 1
Comm object 10569 Related applications All
Config level Standard
Setpoint visibility Always
Description
Delay for Force block protection activation after binary input Force Block 1 is opened. Protection
deactivation is without delay. Protection is activated/deactivated independent on engine running or not
running state.
ForceBlockDel1
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 0
Step 1
Comm object 10570 Related applications All
Config level Standard
Setpoint visibility Always
Description
Delay for Force block protection activation after binary input Force Block 2 is opened. Protection
deactivation is without delay. Protection is activated/deactivated independent on engine running or not
running state.
ForceBlockDel2
6 back to List of setpoints