InteliDrive DCU Marine - 3.0.0 Global Guide
177
Related FW 3.0.0 Related applications All
Comm object 150
Description
If the input is closed following commands received via RS232 or CAN2 interface (e.g. from InteliMonitor or
from remote display) are inactive:
Remote engine start, stop commands
Fault reset and horn reset
Setpoints change
Engine can be started, stopped via Binary inputs (e.g. Remote Start) or via front panel buttons.
Device Command Access lock Remote lock LOC (Local) mode
ID-DCU MARINE panel START N Y Y
STOP N Y Y
FLT RES Y Y Y
HORN RES Y Y Y
Setpoint
change
N Y Y
Mode change N Y Y
ID-DCU MARINE Bin Inputs Remote start Y Y N
Remote stop Y Y N
Remote OFF Y Y N
External modules Bin Inputs ...start/stop Y Y N
Remote OFF Y Y N
Remote HBR Y Y N
(RS232 or CAN2) STOP Y N N
FLT RES Y N N
HORN RES Y N N
Setpoint
change
Y N N
Mode change Y N N
InteliMonitor START Y N N
(serial line) STOP Y N N
FLT RES Y N N
HORN RES Y N N
Setpoint
change
Y N N
Mode change Y N N
InteliDrive local/remote commands blocking overview
Note: Y = available, N = blocked
Remote Lock