InteliDrive DCU Marine - 3.0.0 Global Guide
180
Related FW 3.0.0 Related applications All
Comm object 141
Description
Active input blocks indication of ECU communication fail e.g. in the case the ECU is switched off.
ECUComFailBlck
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 927
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
Outputs Cooling pump and Prelubrication are deactivated as well.
This input cannot be overriden with the input Sd override.
Note: Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
IMPORTANT: This is a software function only. It can be extended by a "hard wired"
emergency stop function, which means disconnecting power supply from the controller
outputs.
EmergencyStop1
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 928
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
Outputs Cooling pump and Prelubrication are deactivated as well.
This input cannot be overriden with the input Sd override.
Note: Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
IMPORTANT: This is a software function only. It can be extended by a "hard wired"
emergency stop function, which means disconnecting power supply from the controller
outputs.
EmergencyStop2
6 back to List of LBI