InteliDrive DCU Marine - 3.0.0 Global Guide
147
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0 YES
Step 0,1
Comm object 10145 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Warning characteristic is defined by two points for Idle RPM and Nominal RPM.CPNomRPMWrn
defines coolant pressure warning level at nominal speed. For details see CoolPrRPMdel (page 148)
description.
CPNomRPMWrn
6 back to List of setpoints
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10146 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.CPIdleRPMSd
defines coolant pressure shutdown level at idle speed. For details see CoolPrRPMdel (page 148)
description.
CPIdleRPMSd
6 back to List of setpoints
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10147 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.CPNomRPMSd
defines coolant pressure shutdown level at nominal speed. For details see CoolPrRPMdel (page 148)
description.
CPNomRPMSd
6 back to List of setpoints