InteliDrive DCU Marine - 3.0.0 Global Guide
148
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 10
Step 1
Comm object 10151 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
RPM dependent Coolant pressure protection delay. Corresponding protection is activated when Coolant
pressure is below limit for CoolPrRPMdel.
To activate RPM dependent coolant pressure protection any analog value has to be linked with LAI: Coolant
Press.
Note: RPM dependent coolant pressure protection is fix configured Protection block type = Engine
running only with RunOnlyBlkDel1 delay.
CoolPrRPMdel
6 back to List of setpoints