Comm object 280
Description
Indicates Ready state for Remote engine start.
RdyForRemStart
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 116
Description
The output closes at the beginning of prestart and opens if the engine shall be stopped.This output can be
used to indicate when the ECU should be powered up i.e. only while the engine is running.
This output also influences evaluation of communication failure with ECU and related FLS alarms from
analog inputs read from the ECU. If the output is configured (which means configured on physical binary
output or VBOUT output), the issuing of communication error is blocked during Prestart and Stopping
procedure as shown in the picture.
Note: The input must be configured on physical binary output or VBOUT output. It is not enough to
configure it as a PLC input for example.
ECU PowerRelay
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 281
Description
1 sec pulse is generated after panel Start button is pressed.
StartButtEcho