InteliDrive DCU Marine - 3.0.0 Global Guide
206
Related FW 3.0.0 Related applications All
Comm object 40
Description
The output closes when engine starts and opens AfterCoolTime delayed after stop the engine.
Cooling Pump
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 81
Description
Indicates correctly running firmware when cycling on/off with 0,5s period.
Watchdog
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 755
Description
Output is closed when panel 0/1 (On/Off) button is pressed or Binary input Remote On/Off is closed and
engine RPM is over Engine protection:MinLoadSpeed.
Output opens when RPM is bellow MinLoadSpeed. Close load can´t be opened by button when Binary input
Remote On/Off (level sensitive) is closed.
Function can be blocked by binary input Load blocking.
Close Load
6 back to List of LBO
Related FW 3.0.0 Related applications AUX, EME, CMB
Comm object 265
Description
The output is closed/opened with rising edge of Binary input Rem On/Off (or I/0 front panel button) when
engine is in Running state and engine RPM is over MinLoadSpeed. Output opens when RPM is below
Close Load (AUX, EME, CMB, only)