Setpoint group Engine params Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 2
Step 1
Comm object 8394 Related applications All
Config level Standard
Setpoint visibility Always
Description
Time the binary output Prestart is active prior to engine start (Start request sending to ECU). Set to zero if
you want to start immediately after Start button is pressed (the Prestart output stays opened). RPM must be
zero during Prestart time otherwise the Starting procedure is not activated.
Prestart Time
6 back to List of setpoints
Setpoint group Engine params Related FW 3.0.0
Range [units] 1 .. 200 [s]
Default value 8
Step 1
Comm object 8234 Related applications All
Config level Standard
Setpoint visibility Always
Description
Amount of time the controller will crank the engine in an attempt to start.
MaxCrank Time
6 back to List of setpoints
Setpoint group Engine params Related FW 3.0.0
Range [units] CMB, EME: 3 ..200 [s], AUX, PRP: 0 .. 200 [-]
Default value 8
Step 1
Comm object 8257 Related applications All
Config level Standard
Setpoint visibility Always
Description
Pause between cranking attempts.
CrankFailPause
6 back to List of setpoints