EasyManuals Logo

ComAp InteliDrive DCU Marine User Manual

ComAp InteliDrive DCU Marine
285 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #200 background imageLoading...
Page #200 background image
InteliDrive DCU Marine - 3.0.0 Global Guide
200
Related FW 3.0.0 Related applications All
Comm object 2
Description
The output closes if any alarm is activated and opens after Fault reset even if the Alarm is still active.
Alarm
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 256
Description
The output closes if any Wrn, Sd, Cd, Fls, alarm is active and stays closed until all alarms disappear and
Fault reset is pressed = output is opened when Alarm list is empty.
Common Alarm
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 3
Description
The output closes when any Warning alarm is active. Output opens when all Wrn alarms disappear and Fault
reset is pressed (no Wrn alarm in Alarm list).
Common Wrn
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 4
Description
The output closes when any Shut-down alarm is active. Output opens when all Sd alarms disappear and
Fault reset is pressed (no Sd alarm in Alarm list).
Common Sd
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 257
Description
The output closes when any Cool-down alarm is active. Output opens when all Cd alarms disappear and
Fault reset is pressed (no Cd alarm in Alarm list).
Common Cd
6 back to List of LBO

Table of Contents

Other manuals for ComAp InteliDrive DCU Marine

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive DCU Marine and is the answer not in the manual?

ComAp InteliDrive DCU Marine Specifications

General IconGeneral
BrandComAp
ModelInteliDrive DCU Marine
CategoryController
LanguageEnglish

Related product manuals