EasyManua.ls Logo

ComAp InteliDrive DCU Marine - Statistics; Runhours; Numsuccstarts; Numunscstarts

ComAp InteliDrive DCU Marine
285 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive DCU Marine - 3.0.0 Global Guide
280
Statistics
Value group Statistics Related FW 3.0.0
Resolution [units] 1 [h]
Comm object 8206 Related applications All
Description
Engine running hours value.
RunHours
6 back to List of values
Value group Statistics Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 8207 Related applications All
Description
Successful engine start number counter. The counter is increased by 1 even if the particular start command
will take more than one attempt.
Note: The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set statistics.
NumSuccStarts
6 back to List of values
Value group Statistics Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 10149 Related applications All
Description
Unsuccessful starts counter. The counter is incremented always when Start fail alarm is issued.
Note: The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set statistics.
NumUnscStarts
6 back to List of values
Value group Statistics Related FW 3.0.0
Resolution [units] 1[-]
Comm object 9648 Related applications All
Description
This is maintenance countdown timer. The timer is located in setpoints group Engine protect as well as in
Statistics values. Adjust the timer to the requested maintenance interval. It will be decremented while the
engine is running. The alarm WrnServiceTime is issued as soon as the timer counts down to zero.
Service Time
6 back to List of values

Table of Contents