InteliDrive DCU Marine - 3.0.0 Global Guide
183
Related FW 3.0.0 Related applications All
Comm object 159
Description
If input is active and Logical Analog input Requested RPM is not valid (out of range, sensor fail),
Loadsharing: ThrottlePos is set to Load sharing: Back Up Speed value. Loadsharing: ThrottlePos = 0,0%
when analog request is out of range and Binary input Back Up Speed is not active.
Back Up Speed
6 back to List of LBI
Related FW 3.0.0 Related applications PRP
Comm object 158
Description
Remote engine start with cranking attempts according to setpoint Engine params Crank Attempts.
RemRepStart (PRP only)
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 160
Description
If active, clutch is disconnected and Loadsharing: ThrottlePos is set to Engine params: FireAlarmSpeed, the
ThrottlePos value change is influenced by ramp specified by Loadsharing: RQSP Ramp.
Fire Speed
6 back to List of LBI
Related FW 3.0.0 Related applications PRP
Comm object 183
Description
If active closes binary output Clutch Connect – see CLUTCH CONNECT (PRP ONLY) (PAGE 202)
Rem Clutch
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 68
Description
OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state (i.e. disables
engine start). It is active in LOC (Local) mode as well.
StartBlocking1
6 back to List of LBI