InteliDrive DCU Marine - 3.0.0 Global Guide
146
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0.. 600 [s]
Default value 10
Step 1
Comm object 10150 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
RPM dependent Oil pressure protection delay. Corresponding protection is activated when Oil pressure is
below limit for OilPrRPMdel.
To activate RPM dependent oil pressure protection any analog value has to be linked with LAI: Oil Press.
Note: RPM dependent oil pressure protection is fix configured Protection block type = Engine running
only with RunOnlyBlkDel1 delay.
OilPrRPMdel
6 back to List of setpoints
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0 YES
Step 0,1
Comm object 10144 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Warning characteristic is defined by two points for Idle RPM and Nominal RPM.CPIdleRPMWrn
defines coolant pressure warning level at idle speed. For details see CoolPrRPMdel (page 148)
description.
CPIdleRPMWrn
6 back to List of setpoints