InteliDrive DCU Marine - 3.0.0 Global Guide
136
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 30
Step 1
Comm object 10025 Related applications All
Config level Standard
Setpoint visibility Always
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel3 (i.e. "running
only", group #3) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
Note:
Engine running state =
RPM > Engine params: Starting RPM or
Analog input Oil Press > Engine params: Starting Poil or
Analog input Coolant Press > Engine params: StartPCoolant (PRP only) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunOnlyBlkDel3
6 back to List of setpoints