EasyManua.ls Logo

ComAp InteliDrive DCU Marine - Pickup Fail; Battery Flat;Battery Volt; Wrnservice Time; Not Lubricated

ComAp InteliDrive DCU Marine
285 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive DCU Marine - 3.0.0 Global Guide
232
Related FW 3.0.0 Related applications All
Comm object
Description
Pickup fail indication. Pickup fail: lost of RPM signal in running state (other running indication is active).
Pickup Fail
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object
Description
ID-DCU MARINE controller reset during Cranking state.
Battery Flat
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 1293
Description
Indication when battery voltage (ID-DCU MARINE power supply) is out of Engine protect: Batt <V and Batt
>V limits.
Battery Volt
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object
Description
Output is closed when Service time (count down) = 0.
Note: History record and Alarm list indication is activated as well.
WrnService Time
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object
Description
The lubrication cycle (PrelubrTime) is not finished after controller Switch on or return from OFF mode.
Not Lubricated
6 back to List of LBO