Setpoint group Engine params Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 60
Step 1
Comm object 9815 Related applications All
Config level Standard
Setpoint visibility Always
Description
Under normal conditions the engine must certainly stop within this period. The period starts by issuing stop
command.
Stop Time
6 back to List of setpoints
Setpoint group Engine params Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 30
Step 1
Comm object 8258 Related applications All
Config level Standard
Setpoint visibility Always
Description
Runtime of unloaded engine to cool down engine before stopping.
Cooling Time
6 back to List of setpoints
Setpoint group Engine params Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 120
Step 1
Comm object 8662 Related applications All
Config level Standard
Setpoint visibility Always
Description
Binary output Cooling Pump is closed when engine starts and opens with AfterCoolTime delay after engine
stopping.
AfterCoolTime
6 back to List of setpoints