InteliDrive DCU Marine - 3.0.0 Global Guide
209
Related FW 3.0.0 Related applications All
Comm object 274
Description
Inverted function to binary output Idle/Nominal. The output closes during engine start, after Idle Time
setpoint elapses. The output closes again after Cooling Time is finished.
Nominal/Idle
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 275
Description
Function is based on Binary output Common Alarm - stays closed when any alarm is active (at least one
item in Alarm list) and opens for 2 sec when any new Alarm is activated. The first activation is delayed 2 sec.
No Fault reset influence when at least one alarm is active. Output opens when Alarm list is empty.
Alarm Blink
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 276
Description
The output is closed when setpoint Basic setting: Idle/Nominal = NOMINAL or Idle/Nominal = BIN.INPUT
and corresponding Binary input BI Nominal is closed. This logical output (Source) can be configured to
corresponding J1939 output (e.g. Idle Speed Select in Volvo-IndustrialD12 Aux).
Idle Sw
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 26
Description
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).
Logical 0
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 27
Description
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).
Logical 1
6 back to List of LBO