Bargraph
100%
Bargraph ending value.
Function Select from the list if function is required or leave free if input is a protection only.
Offset Measured value offset.
Note: Some configuration items (e.g. Protection) stay without change when Property - Sensor is changed to
None.
Sensors availability
Sensors available on ID-DCU MARINE
AI1 - AI4
Resolution Sensor range HW jumper
Pt1000/°C, Ni1000/°C,
Pt1000/°F, Ni1000/°F
Fix, not configurable Resistance: 3-4
4-20 mA active,
±20 mA active (measures + only)
Adjustable -
see Hint
below.
For 20 mA input Current: 1-2
0-250 Ω, 0-2400 Ω
For 250 or 2400 Ω
Input
Resistance: 3-4
Tristate Resistance: 3-4
0 to 4 VDC Adjustable Voltage: 2-3
Sensors available on ID-DCU MARINE
AI5 - AI8
Resolution Sensor range HW jumper
Pt100/°C, Pt1000/°C, Ni100/°C, Ni1000/°C,
Pt100/°F, Pt1000/°F, Ni100/°F, Ni1000/°F
Fix, not configurable Resistance: 3-4
Thermocpl J/°C, Th K/°C, Th/°C,
Thermocpl J/°F, Th. K/°F, ThL/°F
Fix, not configurable Voltage: 2-3
4-20 mA active, ±20 mA active
Adjustable -
see Hint below.
For 20 mA input Current: 1-2
0-250 Ω, 0-2400 Ω
For 250 or 2400 Ω
input
Resistance: 3-4
±1 V, 0-100 mV For 1V or 100mV Voltage: 2-3
Tristate Resistance: 3-4
0 to 5 VDC Adjustable Voltage: 2-3
Configuration examples
Conversion from 4-20 mA to 6.0 Bar Oil pressure sensor (Wrn+Sd protection and Oil press function)