InteliDrive DCU Marine - 3.0.0 Global Guide
124
Setpoint group Engine params Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 10,0
Step 0,1
Comm object 9681 Related applications All
Config level Standard
Setpoint visibility Always
Description
Oil pressure limit when controller stops cranking = one of the engine running indications.
To activate this function any Analog input must be configured to Analog logical input Oil press.
Note: Step, Range and dimension depend on corresponding Analog input sensor characteristic.
Starting POil
6 back to List of setpoints
Setpoint group Engine params Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 10,0
Step 0,1
Comm object 10138 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Coolant pressure limit = one of the engine running indications. To activate this function any Analog input
must be configured to Analog logical input Coolant press.
Note: PRP only
Note: Step, Range and dimension depend on corresponding Analog input sensor characteristic.
StartPCoolant
6 back to List of setpoints