InteliDrive DCU Marine - 3.0.0 Global Guide
185
Related FW 3.0.0 Related applications All
Comm object 46
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Engine params: Starting RPM or
Analog input Oil pressure > Engine params: Starting Poil or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunIndication1
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 47
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Engine params: Starting RPM or
Analog input Oil pressure > Engine params: Starting Poil or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunIndication2
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 48
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Engine params: Starting RPM or
Analog input Oil pressure > Engine params: Starting Poil or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunIndication3
6 back to List of LBI