InteliDrive DCU Marine - 3.0.0 Global Guide
126
Setpoint group Engine params Related FW 3.0.0
Range [units] CMB, EME: 0 .. 200 [-], AUX, PRP: 1 .. 200 [-]
Default value 3
Step 1
Comm object 8255 Related applications All
Config level Standard
Setpoint visibility Always
Description
Max number of crank attempts.
CMB, EME: Setting to 0 means unlimited number of starting attempts.
Note: There is one start attempt only in case of panel Start button or Binary input Remote Start
activation. Number of Cranking attempts based on this setpoint is accepted when start is activated by
Binary input RemRepStart (PRP) or Blackout Start (AUX, EME and HRB) only. The setpoint is not
followed if Sd Override is active, crank attempts number is then unlimited in case of Blackout Start.
Together with request of unlimited start attempts was created LBI PrestartOverride - activation means
immediate transition from state Prestart to Cranking.
Same function was applied to second push of START button. First press of START button activates state
Prestart, second press of START button skips prestart period.
Crank Attempts
6 back to List of setpoints
Setpoint group Engine params Related FW 3.0.0
Range [units] Starting RPM.. Nominal RPM [RPM]
Default value 500
Step 1
Comm object 9946 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Default Idle speed (should be the same as Idle speed set with engine ECU).
Idle RPM
6 back to List of setpoints