InteliDrive DCU Marine - 3.0.0 Global Guide
231
Related FW 3.0.0 Related applications All
Comm object
Description
Intercontroller communication error.
OthrCommEr
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object
Description
Charger fail detection. D+ output current is limited to cca 300 mA.
Guaranteed level for signal Charging OK = 90% of supply voltage.
There are three possible conditions for stop engine cranking: Starting RPM, StartingPOil and D+ function
(when ENABLED). Starter goes off when any of these conditions becomes valid.
ChrgAlternFail
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object
Description
Engine stop fail indication. Stop fail: engine does not reach 0 RPM after stop command within Engine
params: Stop time.
Stop Fail
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object 779
Description
Engine overspeed indication.
Overspeed
6 back to List of LBO
Related FW 3.0.0 Related applications All
Comm object
Description
Under speed indication.
Underspeed
6 back to List of LBO

Table of Contents

Other manuals for ComAp InteliDrive DCU Marine

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive DCU Marine and is the answer not in the manual?

ComAp InteliDrive DCU Marine Specifications

General IconGeneral
BrandComAp
ModelInteliDrive DCU Marine
CategoryController
LanguageEnglish

Related product manuals