InteliDrive DCU Marine - 3.0.0 Global Guide
186
Related FW 3.0.0 Related applications All
Comm object 41
Description
Skips Idle Time and switch controller from Idle to Running state when closed before Idle Time is over.
Nominal Speed
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 162
Description
Binary input function for loaded engine indication.
Loaded
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 45
Description
This input is designed to allow the engine to be controlled externally, not by the controller. This feature is
especially designed for marine gen-sets, which are supposed to be started manually as the controller has no
power supply before the gen-set is started. It may be also useful in case of testing the gen-set or in case of a
failure, which does not allow the gen-set to be controlled by the controller, but the gen-set itself is stays
operational.
The controller behaves following way:
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the engine control, deactivates all outputs related to it except Fuel
Solenoid.
Stop Fail alarm is not being evaluated and Stop Solenoid is not activated if nonzero speed is
detected.
When the input is deactivated, the controller takes control over the engine according to the situation
in which the gen-set was in the moment of deactivation. I.e. the engine remains running if it was
running in the moment the input was deactivated.
Emerg. Manual
6 back to List of LBI
Related FW 3.0.0 Related applications PRP
Comm object 163
Description
Binary input activates Engine start via clutch. Engine is started by the other running engine via closed clutch
- binary output Clutch Connect. See MaxClStrtPer (page 156) protection setpoint.
EnClutchStart
6 back to List of LBI