InteliDrive DCU Marine - 3.0.0 Global Guide
141
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. Starting RPM [RPM]
Default value 30
Step 1
Comm object 8260 Related applications All
Config level Standard
Setpoint visibility Always
Description
Underspeed alarm is activated when engine is running and actual RPM is below the UnderSpeed threshold.
UnderSpeed
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. Nominal RPM [RPM]
Default value 500
Step 1
Comm object 10139 Related applications All
Config level Standard
Setpoint visibility Always
Description
Binary output Ready to load is closed if RPM > MinLoadSpeed and engine is in Running state. Use this
output to enable/disable connecting of engine load. MinLoadSpeed is a condition to close BO Close Load
when panel I/0 button is used to connect load to engine.
MinLoadSpeed
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.0.0
Range [units] Batt <V.. 40,0 [V]
Default value 30,0
Step 0,1
Comm object 9587 Related applications All
Config level Standard
Setpoint visibility Always
Description
Warning level for battery over voltage.
Batt > V
6 back to List of setpoints